Short answer
Start with the loop powered and the meter in the correct current range. Place the meter in series, not across the two loop terminals. A current measurement made in parallel can create a short circuit and damage equipment.
What to look for
First measure the supply voltage at the transmitter terminals. If the supply is absent, the loop cannot produce a meaningful current. If the supply is present, inspect polarity, terminal tightness, and the receiving input's load.
Then move the meter one point at a time. A reading that appears on one side of the transmitter but disappears on the other usually tells you where the circuit opens. Do not replace the transmitter until the loop has been proved continuous.
When the symptom appears in the plant
An operator reported that a tank level indicator suddenly dropped to 0%, shutting down the transfer pumps. The maintenance technician found the local display blank. Further investigation revealed that the 24V DC loop power supply had blown a fuse due to a crushed conduit that shorted the two-wire transmitter cable to the grounded pipe. The 0mA reading correctly indicated a complete loop failure rather than an actual empty tank.
Five checks before replacement
- Check the loop power supply with a multimeter to ensure it is delivering 24V DC across the loop.
- Inspect all field wiring, terminal blocks, and splices for loose connections, broken wires, or visible damage.
- Disconnect the field device and use a loop calibrator to inject 4-20mA directly into the PLC input to isolate whether the issue is in the field or the cabinet.
- Verify the integrity of the transmitter by checking its local display (if equipped) or testing it with a bench power supply.
- Check the PLC analog input card for blown internal fuses or diagnostic error flags in the control software.
A reading of 0mA always means a broken circuit or dead power supply; a true zero measurement should read 4mA.
Always check the cheapest components first: fuses, loose terminal screws, and quick-disconnect plugs.
In a series loop, one failed device or loose wire takes down the entire signal.
Bench checklist
- Confirm the supply at the device terminals.
- Confirm the meter is in the correct mode and position.
- Confirm the input range matches the signal type.
- Confirm the reference/common is intentional.
- Record the reading before changing the wiring.
Reference families
- ISA-50.1 Standard
- Instrument Troubleshooting Guides
Always verify the current edition and the exact device manual for the installation.
Official references
These links point to standards bodies, industry organizations, or manufacturer documentation. Standards landing pages may require purchase or institutional access.
- What Is a 4-20 mA Current Loop? Fluke
Explains live zero and why 0 mA commonly indicates an interruption or power fault.
- How to measure a 4-20mA loop signal Fluke
Official measurement sequence for transmitter, wiring, input card, and return path.
- ISA50, Signal Compatibility of Electrical Instruments ISA
Official standards information page for 4–20 mA instrumentation signals.
- ControlLogix HART Analog I/O Modules User Manual Rockwell Automation
Official manual documenting open-wire diagnostics and the distinction between 4–20 mA and 0–20 mA modes.