PRINTABLE FIELD REFERENCE · A4 / LETTER

Industrial I/O
Pocket Card.

Designed for noisy, zero-signal plant floors. Print, fold in half, and keep inside your multimeter pouch or tape directly inside the enclosure door.

Direct PDF download link included. Strictly technical updates only.
Optimized for standard 2-page duplex print
POCKET SPECIFICATION
  • Dimensions: 105 × 148 mm (Folded A6) or full Letter/A4
  • Target Paper: 160–250 gsm cardstock (or laminate)
  • Standards: IEC 61076, IEC 61131, ISA-50, NAMUR NE 43
  • Color Code: High-contrast industrial wire sequences
SIGNAL FIELD GUIDE · POCKET CARD
4–20 mALive Zero
M12/M8Wire Colors
PNP/NPNCommon Logic
24V DCDrop Budget
PANEL 1

4–20 mA Current Loops & NAMUR NE 43

Loop Voltage Headroom Formula: V_transmitter = V_supply − (I_max × R_total_loop)

Transmitter terminal voltage must stay ≥ 12.0 V DC at 20.5 mA.

Signal Level Percentage Diagnostic Condition (NAMUR NE 43)
0.00 mA Open / Dead Broken wire, blown fuse, or dead 24V supply.
< 3.60 mA Under-range Sensor failure or broken sensing element.
3.80 mA -1.25% Permissible under-range baseline.
4.00 mA 0.0% True Process Zero (Live Zero).
12.00 mA 50.0% Midpoint span reading.
20.00 mA 100.0% Full Scale Process Upper Range.
20.50 mA 103.1% Permissible over-range limit.
> 21.00 mA Fault Short Sensor short circuit or severe electronics fault.
Meter Hookup: Multimeter MUST be in series with loop current. Parallel multimeter probe hookup creates a short circuit and blows the meter fuse.
PANEL 2

DC 3-Wire Sensor Switching (PNP vs NPN)

Sensor Type Switching Action PLC Input Required PLC Common Tie
PNP (Sourcing) Switches +24 V DC to signal line Sinking Input Card Common terminal tied to 0 V DC
NPN (Sinking) Switches 0 V DC to signal line Sourcing Input Card Common terminal tied to +24 V DC
Standard 3-Wire DC Sensor Wire Colors (IEC 60947-5-2):
  • Brown (BN): +24 V DC Power Supply (+19.2V to +28.8V)
  • Blue (BU): 0 V DC Reference Return
  • Black (BK): Switched Output 1 (Normally Open / NO)
  • White (WH): Output 2 / Normally Closed (NC) / Antivalent
Ghost Voltage Trap: High-impedance digital multimeters may measure 2V–8V on an open sensor output. Use a 10 kΩ pull-down resistor or low-impedance meter (LoZ) to verify true switching.
PANEL 3

M12 & M8 Circular Connector Pinouts

Connector Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 / FE
M12 A-4 Brown (+24V) White (NC) Blue (0V) Black (NO) —
M12 A-5 Brown (+24V) White (Aux) Blue (0V) Black (C/Q) Gray (FE / Shield)
M12 D-4 (ETH) Yellow (Tx+) White (Rx+) Orange (Tx−) Blue (Rx−) Shell 360° Shield
M12 B-5 (DP) +5V (VP) Green (Line A) 0V (DGND) Red (Line B) Shield Ground
M8 A-3 Brown (+24V) OMITTED Blue (0V) Black (NO) —
M8 A-4 Brown (+24V) White (NC) Blue (0V) Black (NO) —
CRITICAL TRAP: Pin numbers mirror horizontally across mating faces! Looking into male pins: Pin 1 is top right. Looking into female sockets: Pin 1 is top left.
Torque Specs: M12 knurled nut: 0.6 Nm · M8 knurled nut: 0.4 Nm. Never use pliers on knurled couplings.
PANEL 4

Noise, RS-485 Modbus & Voltage Drop

5-Point Enclosure Noise Checklist:
  1. Shield Termination: Ground cable shield at ONE end only (cabinet end) for low-frequency analog loops to prevent ground circulating currents.
  2. RS-485 Bus Termination: Exactly two 120 Ω resistors at the two physical cable ends. Total unpowered line resistance across A & B must measure 60 Ω.
  3. Modbus Idle Bias: Pin 4 (Line B) must measure +0.8V to +1.2V DC higher than Pin 2 (Line A) relative to 0V ground.
  4. Inductive Kickback: Place a reverse flyback diode (1N4007) across DC solenoids, or an RC snubber across AC contactor coils.
  5. 24V DC Cable Drop Limit: Ensure sensor terminal voltage stays > 20.4 V DC under maximum inrush load.
Conductor Loop Resistance (Copper @ 20°C): R_loop = 2 × Length (m) × Conductor Resistance (Ω/m)

22 AWG (0.34 mm²) = ~0.057 Ω/m · 18 AWG (0.82 mm²) = ~0.021 Ω/m