BENCH TOOLS / 01

Numbers you can
use at the cabinet.

Small calculators for translating a reading into the next sensible question. No account. No spreadsheet ceremony.

FIELD
READY
01

4–20 mA converter

Translate a measured current into engineering units.

FORMULAlow + ((mA − mAmin) ÷ (mAmax − mAmin)) × (high − low)
ENGINEERING VALUE50.000 to 100 range
4 mA20 mA

Inside the configured range. The signal is giving you a usable reading.

02

Loop load check

Estimate the voltage consumed by a known loop resistance.

At 12.00 mA, this resistance uses3.00 Vleaving approximately 21.00 V for the transmitter and input.
4–20 mA current loop diagramTWO-WIRE CURRENT LOOP24 V DCSUPPLYTRANSMITTER4–20 mAPLC AIINPUT+ loopsignalreturn / common
03

Signal quality, by symptom

A quick handoff from number to next check.

01Stable but wrong

Check scaling, range selection, and whether the input expects current or voltage.

02Wandering value

Check routing near drives, shield termination, reference points, and loose terminals.

03Zero or saturated

Check supply, polarity, continuity, and the input card’s live-zero configuration.