Short answer

Pin 1 is +24V (Brown), Pin 2 is NC/Signal 2 (White), Pin 3 is 0V (Blue), Pin 4 is NO/Signal 1 (Black).

Under industrial standard IEC 61076-2-101, the keyway orientation governs terminal positions. Always verify whether you are inspecting male pins or female contact sockets; pin sequences mirror horizontally across mating faces.

Mating face vector schematic

Compare the male plug and female socket pin positions before terminating wires or taking multimeter readings.

A-Coded · 4-PIN CONNECTOR FACE SCHEMATIC
IEC 61076-2-101
MALE PLUG (PINS) Looking into pins of male cordset 1 2 3 4 FEMALE SOCKET (HOLES) Looking directly into sensor or bulkhead socket 1 2 3 4
IEC Color Code Reference:
Pin 1: Brown (BN)
Pin 2: White (WH)
Pin 3: Blue (BU)
Pin 4: Black (BK)
Deterministic schematic · M12 A-Coded 4-Pin Connector (IEC 61076-2-101). Gold contacts indicate male pins; dark rings indicate female sockets.

Physical & electrical specifications

M12 A-Coded 4-Pin Connector Engineering Boundaries
Specification Parameter Standard Value Practical Field Implication
Governing Standard IEC 61076-2-101 Guarantees dimensional interoperability between manufacturers (Siemens, Phoenix Contact, Turck, Murr).
Mechanical Keyway Single polarizing keyway notch at 12 o’clock position on male plug, mating tab on female receptacle. Prevents accidental cross-mating into incompatible communication or power ports.
Coupling Nut Torque 0.6 Nm (hand-tight + 1/4 turn with knurled wrench) Excess torque crushes the internal elastomeric O-ring, causing coolant leaks and intermittent shorts.
Rated Voltage 250 V AC/DC Maximum dielectric insulation boundary between adjacent conductor pins.
Rated Current Limit 4 A per contact Continuous current carrying capacity per pin without thermal de-rating.
Recommended Wire Gauge 22 AWG to 20 AWG (0.34 mm² to 0.50 mm²) Conductor strand cross-section required to maintain terminal contact and pull-out strength.
Ingress Protection IP67 / IP68 (when properly torqued with intact O-ring) Submersion and high-pressure washdown seal integrity when fully threaded.

Pin assignment & multimeter test values

Measure between the designated pin and reference ground with a digital multimeter in DC Volts mode.

Standard Terminal & Conductor Assignments
Pin # Standard Color Signal Designation Operating Voltage Multimeter Test Method
Pin 1
Brown (BN)
+24 V DC Power Supply +19.2 to +28.8 V DC DC Volts across Pin 1 (+) and Pin 3 (-). Must read nominal +24 V DC.
Pin 2
White (WH)
Complementary / NC / Diagnostic Output 0 V DC (OFF) or +24 V DC (ON) DC Volts across Pin 2 and Pin 3. Active when sensor is unactuated on NC sensors.
Pin 3
Blue (BU)
0 V DC (Common Ground / Return) 0.00 V DC reference DC Volts across Pin 3 and chassis earth (<0.5 V DC). Continuity to panel 0 V bus.
Pin 4
Black (BK)
Switched Output (NO) / IO-Link C/Q Line 0 V DC (OFF) or +24 V DC (ON) DC Volts across Pin 4 and Pin 3. Transitions to +24 V DC when target engages PNP sensor.

Meter-first 3-step field diagnostic sequence

Perform these 3 tests in order before swapping field devices or cutting cable bundles.

  1. Step 1: Measure Open-Circuit Supply Voltage

    Action: Unplug sensor. Set multimeter to DC Volts. Insert red lead into Female Pin 1 (Brown) and black lead into Female Pin 3 (Blue).

    Expected Reading: +20.4 V to +27.6 V DC (IEC 61131-2 Type 1/3 limit).

    Fault Symptom: If reading is 0V, inspect panel fuse, distribution block terminal tightness, or severed cable in drag chain.

  2. Step 2: Verify Output Switching Under Load

    Action: Reconnect sensor using a breakout box or backprobe Pins 3 & 4. Toggle target in front of sensor face while observing meter.

    Expected Reading: 0.0 V DC (target absent) -> +23.2 V DC (target present, <1.0 V drop below supply).

    Fault Symptom: If output voltage stays floating (e.g., 2V to 8V), the sensor output transistor is damaged or the PLC input lacks a solid 0V common reference.

  3. Step 3: Inspect Drag Chain Conductor Fatigue

    Action: Switch multimeter to Ohms (Audible Continuity). Measure Pin 3 (Blue) to panel 0V while manually flexing the cable along flex-points.

    Expected Reading: <0.8 Ω steady continuous resistance.

    Fault Symptom: Intermittent beeping or resistance jumps above 5 Ω reveal fractured copper stranding inside polyurethane jacket.

Field traps & common failure modes

Field Trap: Male vs. Female Face Mirroring Error

Male vs. Female Face Mirroring Error

Observed Symptom: Technician replaces cordset and burns sensor internal circuit immediately upon power-up.

Root Cause: Pin numbering mirrors across mating planes: Pin 1 and Pin 2 flip horizontal orientation when looking into male pins vs female sockets.

Field Correction: Always verify terminal numbers embossed into the plastic contact carrier or check wire colors before soldering or terminating.

Field Trap: Over-Torquing Knurled Coupling Nut

Over-Torquing Knurled Coupling Nut

Observed Symptom: Intermittent water ingress and corrosion faults after washdown cycles.

Root Cause: Using channel-lock pliers compresses the internal silicone O-ring past its yield point, tearing the seal.

Field Correction: Tighten knurled coupling nut to 0.6 Nm using an industry torque wrench with an M12 crowfoot attachment.

Industrial protocols & applications

Standard Network & Signal Implementations
Network / Protocol Standard Application Reference Standard
Standard Discrete DC Sensors Inductive, capacitive, and photoelectric proximity switches operating in PNP or NPN mode. IEC 60947-5-2
IO-Link Port Class A Point-to-point digital communication on Pin 4 (C/Q) with 24V auxiliary power. IEC 61131-9
Solid-State DC Actuators Pneumatic valve solenoid coils and stack lights pulling up to 2A continuous. ISO 13849

Frequently asked field questions

What is the color code for an M12 4-pin A-coded sensor cable?

Under IEC 60947-5-2 and IEC 61076-2-101, standard M12 4-wire color code is: Pin 1 = Brown (+24V DC), Pin 2 = White (NC / Signal 2), Pin 3 = Blue (0V DC), and Pin 4 = Black (NO / Switched Output 1).

Why does an M12 4-pin sensor read 24V supply but refuse to trigger the PLC input?

The PLC input module common may be mismatched: a PNP sensor sources +24V and requires a sinking PLC input card (common tied to 0V). If the PLC card common is wired to +24V (expecting NPN), no current flows.

FIELD POCKET COMPANION · PRINTABLE PDF

Tape this inside the enclosure door.

No signal on the plant floor? Get the 2-page laminated pocket card. Contains 4–20 mA NAMUR thresholds, PNP/NPN PLC common logic, M12/M8 pin numbers, and 24V DC voltage drop rules.

Fits in Fluke meter pouch
100% offline printable vector
Zero marketing slop
Instant delivery. Strictly technical updates. Unsubscribe anytime.
MV
FIELD INSTRUMENTATION & CONTROLS SPECIALIST

Marcus Vance, PE

16+ Yrs Field Exp

Marcus is a licensed Professional Engineer specializing in industrial process automation, PLC/DCS I/O commissioning, and instrumentation troubleshooting across petrochemical and manufacturing facilities.

Peer-reviewed for IEC & ISA standards compliance · Editorial methodology →
Explore Related Field Guides: